This paper reports a natural ventilation silencer for an animal cage having considerable sound insertion loss. Many veterinary hospitals face a serious problem that hospitalized animals are stressed from the barks of other dogs in the hospital. To address this problem, a solution that barely affects caged dogs’ health is required. First, we estimated aperture ratio of the silencer device which was considered by physiological sustainability of dog. Next, we attempted to use a silencer with sound insertion loss by attaching it to an opening side of the cage. We constructed the tested prototype silencers by using the resonance of a rectangular room and a nonwoven fabric. We measured the acoustic characteristics of the silencers that were attached to the real scale model of the animal cage. We also measured their insertion loss by considering the estimated frequency characteristics of the dogs’ barking sound. The result shows that proposed silencers have more than 10 dB insertion loss; therefore, they can maintain respiratory environment of a caged dogs along with good visibility.
Published in | International Journal of Mechanical Engineering and Applications (Volume 2, Issue 1) |
DOI | 10.11648/j.ijmea.20140201.14 |
Page(s) | 18-24 |
Creative Commons |
This is an Open Access article, distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution and reproduction in any medium or format, provided the original work is properly cited. |
Copyright |
Copyright © The Author(s), 2014. Published by Science Publishing Group |
Noise Control, Sound Insertion Loss, Resonance of Rectangular Room, Cell-type Silencer, Nonwoven Fabric
[1] | N. Hashimoto, Questionnaire on neighborhood noise dispute to person in charge of noise problem in municipal office, AIJ Journal of Technology and Design, Vol. 13, No. 25, 2007, pp 171-176. |
[2] | Ministry of environment (Japan), The 3rd investigative committee of the state of protection management of animal (Document 2 Occurrence situations of harms and troublesome problems), Government of Japan, 2004, pp. 19-21. http://www.env.go.jp/nature/dobutsu/aigo/2_data/arikata/h16_03/mat03.pdf |
[3] | "Air-conditioning / Sanitary Engineering Handbook" Vol.1, Edited and published by Society of Heating, Air-Conditioning and Sanitary Engineers of Japan, 1963, pp. 320-321, NCID: BA53189532. |
[4] | Society of researches for textbook of environment engineering, "Textbook of Environment Engineering", Shokokusha publishing co., ltd., 2000, pp. 134-143, ISBN: 4395005160. |
[5] | M. Tsuboi, "Dog Anatomy and Table for Physiological Calculation", Bunkyo-shoin, 1971, p.195, NCID: BN06961627. |
[6] | T. Tsuda,."Domestic Animal Physiology", Yokendo, 2004, p. 133, NCID: BA66764054. |
[7] | M. Miura, "Architectural Environment Engineering", Morikita Publishing Co., Ltd., 2006, pp. 285-286, ISBN: 9784627581111. |
[8] | U. Inoue, "Duct Calculation Handbook", Kurimoto, Ltd., 1962, pp. 121-122, NCID: BN11470089. |
[9] | S. Sakamoto, T. Miyairi, A. Hoshino, I. Kourakata, T. Sato, "Attenuation characteristics of double orifice silencer jointed by permeable membrane (measurement and theoretical analysis of sound transmission loss)", Transactions of the Japan society of Mechanical Engineers, Series C, Vol. 79, No. 806, 2013, pp. 3474-3486. |
[10] | Z. Maekawa, M. Morimoto, K. Sakagami, "Architectual・Environmental Acoustics 2nd edition", Kyoritsu publishing CO., LTD., 2000, pp. 80-81. |
[11] | R. H. Bolt, S. Labate, U. Ingård, "The acoustic reactance of small circular orifices", J. Acoust. Soc. Am. Vol. 21, No. 2, 1949, pp. 94-97. |
[12] | H. Sasao, "A guide to acoustic analysis by Excel - Analysis of an acoustic structural characteristic - (4) Analysis of the duct system silencer by Excel", Journal of the Society of Heating, Air-Conditioning and Sanitary Engineers of Japan, Vol. 81, No. 1, 2007, pp. 51-58. |
APA Style
Shuichi Sakamoto, Yuichi Toyoshima, Nobuaki Murayama, Toru Miyairi, Akira Hoshino, et al. (2014). Sound Attenuation Devices for Dogs Barking (Estimation of Aperture Ratio and Experimental Study of Silencer). International Journal of Mechanical Engineering and Applications, 2(1), 18-24. https://doi.org/10.11648/j.ijmea.20140201.14
ACS Style
Shuichi Sakamoto; Yuichi Toyoshima; Nobuaki Murayama; Toru Miyairi; Akira Hoshino, et al. Sound Attenuation Devices for Dogs Barking (Estimation of Aperture Ratio and Experimental Study of Silencer). Int. J. Mech. Eng. Appl. 2014, 2(1), 18-24. doi: 10.11648/j.ijmea.20140201.14
AMA Style
Shuichi Sakamoto, Yuichi Toyoshima, Nobuaki Murayama, Toru Miyairi, Akira Hoshino, et al. Sound Attenuation Devices for Dogs Barking (Estimation of Aperture Ratio and Experimental Study of Silencer). Int J Mech Eng Appl. 2014;2(1):18-24. doi: 10.11648/j.ijmea.20140201.14
@article{10.11648/j.ijmea.20140201.14, author = {Shuichi Sakamoto and Yuichi Toyoshima and Nobuaki Murayama and Toru Miyairi and Akira Hoshino and Takatsune Narumi}, title = {Sound Attenuation Devices for Dogs Barking (Estimation of Aperture Ratio and Experimental Study of Silencer)}, journal = {International Journal of Mechanical Engineering and Applications}, volume = {2}, number = {1}, pages = {18-24}, doi = {10.11648/j.ijmea.20140201.14}, url = {https://doi.org/10.11648/j.ijmea.20140201.14}, eprint = {https://article.sciencepublishinggroup.com/pdf/10.11648.j.ijmea.20140201.14}, abstract = {This paper reports a natural ventilation silencer for an animal cage having considerable sound insertion loss. Many veterinary hospitals face a serious problem that hospitalized animals are stressed from the barks of other dogs in the hospital. To address this problem, a solution that barely affects caged dogs’ health is required. First, we estimated aperture ratio of the silencer device which was considered by physiological sustainability of dog. Next, we attempted to use a silencer with sound insertion loss by attaching it to an opening side of the cage. We constructed the tested prototype silencers by using the resonance of a rectangular room and a nonwoven fabric. We measured the acoustic characteristics of the silencers that were attached to the real scale model of the animal cage. We also measured their insertion loss by considering the estimated frequency characteristics of the dogs’ barking sound. The result shows that proposed silencers have more than 10 dB insertion loss; therefore, they can maintain respiratory environment of a caged dogs along with good visibility.}, year = {2014} }
TY - JOUR T1 - Sound Attenuation Devices for Dogs Barking (Estimation of Aperture Ratio and Experimental Study of Silencer) AU - Shuichi Sakamoto AU - Yuichi Toyoshima AU - Nobuaki Murayama AU - Toru Miyairi AU - Akira Hoshino AU - Takatsune Narumi Y1 - 2014/03/20 PY - 2014 N1 - https://doi.org/10.11648/j.ijmea.20140201.14 DO - 10.11648/j.ijmea.20140201.14 T2 - International Journal of Mechanical Engineering and Applications JF - International Journal of Mechanical Engineering and Applications JO - International Journal of Mechanical Engineering and Applications SP - 18 EP - 24 PB - Science Publishing Group SN - 2330-0248 UR - https://doi.org/10.11648/j.ijmea.20140201.14 AB - This paper reports a natural ventilation silencer for an animal cage having considerable sound insertion loss. Many veterinary hospitals face a serious problem that hospitalized animals are stressed from the barks of other dogs in the hospital. To address this problem, a solution that barely affects caged dogs’ health is required. First, we estimated aperture ratio of the silencer device which was considered by physiological sustainability of dog. Next, we attempted to use a silencer with sound insertion loss by attaching it to an opening side of the cage. We constructed the tested prototype silencers by using the resonance of a rectangular room and a nonwoven fabric. We measured the acoustic characteristics of the silencers that were attached to the real scale model of the animal cage. We also measured their insertion loss by considering the estimated frequency characteristics of the dogs’ barking sound. The result shows that proposed silencers have more than 10 dB insertion loss; therefore, they can maintain respiratory environment of a caged dogs along with good visibility. VL - 2 IS - 1 ER -